S3 Layout Re-split
The S3 re-split moves the facility from four production rooms to three rooms plus the buffer spine. The three decisions below record why the Editing Suite was removed and its footprint merged into a widened, high-ceiling Video/Podcast room, why a new external Control Room door (D5) was added, and how the Control Room first-reflection panels are set.
The four-room split forced the east zone into a cramped 11.23 m² video studio and a small 8.56 m² editing suite, separated by an internal partition (Wall 7) and its door (D4). Editing is a quiet, non-critical activity (the old NC-25 target) that does not need a dedicated acoustically-isolated room — it can be performed at any workstation, including inside the Control Room or Video/Podcast space. Dedicating an isolated room to it wasted the most valuable floor area in the facility.
Removing the Editing Suite lets the entire east zone become a single Video/Podcast room of 19.78 m². Freed of the internal Wall 7 / D4 partition, the room also gains a high 3.40 m clear ceiling. A Rev2 laser survey found the true slab-to-slab at 366.4 cm — not the 340 cm assumed on the old drawings — so the height chain is now measured, not estimated: 366.4 slab − 15 cm floated floor − 11 cm compact decoupled ceiling leaf = 340 cm clear, with the hanging MEP (HVAC unit and black pipe) boxed into a perimeter bulkhead with an HVAC service hatch. The larger volume (67.3 m³) pushes the Schroeder frequency down to 130 Hz and spreads the room modes more evenly, giving a well-behaved, flexible space for multi-camera video, podcast panels, and small live sessions. Two weak partition elements (Wall 7 and door D4) are eliminated entirely.
Backdrop — curtain, not a hard cyclorama. The earlier scheme called for a plastered NE coved cyclorama (a fixed, hard, curved corner). Rev3 replaces it with a multi-colour curtain backdrop system: a motorised track on an independent secondary-steel frame hung from the structural slab on neoprene isolation hangers (never off the resilient ceiling leaf, never rigidly through to the slab, to keep the flanking path short), 40 cm off the wall, wrapping the North wall (full) plus the East wall north-half around the NE corner (≈23 m² face). It carries interchangeable heavy velour/molton curtains (≥300 g/m², ≥100 % fullness) in chroma green, white, black molton and mid-grey, plus a vinyl floor-sweep for the infinity curve. Acoustically this is the better decision: fabric absorbs, acting as the room's primary variable mid/high absorber, whereas the hard cyclorama would have added two reflective corner walls. It also frees the wall-panel count (the curtain now carries the video mid/high), so the room drops from 20 wall panels to 6. The camera still shoots toward the backdrop.
RT60 mid 0.284 s (flat green-screen reference) · NC-18 · Schroeder 130 Hz
Treatment: 6 wall panels · 6 deep superchunk traps (400–600 mm) · 4 membranes (≈123 Hz) · deep perimeter bass soffit · in-shot area rug (≈6 m²) · isolated Unistrut lighting grid · lean 28% ceiling cloud · multi-colour curtain backdrop (N + E-half)
In the four-room layout the Control Room was reached only through the buffer spine or from VO Live (D3). With the east-zone re-split and the removal of the old Editing access, the Control Room needed its own external entry so engineers can come and go without transiting VO Live or the buffer during a take. (The old buffer↔Control door D2 has since been deleted in Rev2 — Control is now entered only by external D5.)
D5 is a new STC 50 acoustic door (90 × 220 cm) on the south wall. It matches the STC 50 perimeter-shell/entry standard (same as D1), so it introduces no weak link in the envelope. It opens outward for clean egress and to avoid any swing conflict with the console and the side-wall first-reflection panels inside the room. Routing Control traffic through its own door reduces footfall-borne disturbance in VO Live and the buffer spine during recording.
Swing: outward · Role: dedicated Control Room external entry
A corners-only Control Room treatment — bass traps in all corners, QRD diffusers on the rear wall, ceiling cloud — would meet the RT60 target of 0.30s without any flat absorption panels on the side walls. The RT60 number would be correct. However, RT60 does not capture early reflections.
In a nearfield monitoring environment, the primary acoustic concern after RT60 is the first reflection points — the spots on the left and right walls where direct sound from the monitors bounces once before reaching the mix position. Untreated, these reflections arrive 5–15 ms after the direct sound, causing comb filtering that colours the frequency response and compromises stereo imaging. This is audible on every mix as a smeared centre image and unreliable low-mid decisions.
Three panels — at the first reflection points on the east and west side walls (~120 cm AFF, positioned by mirror method from the mix position) plus an absorptive/splayed front — eliminate this artefact without over-damping the room. The room is too small for a time-based reflection-free zone (ITDG under 15 ms), so the RFZ is achieved by absorbing the E/W first-reflection points directly. The resulting mid-band RT60 of approximately 0.307s sits in the preferred range for broadcast monitoring. Heavier flat absorption was rejected: it would over-damp the larger 6.97 m² Control Room and lose the natural reverb tail needed for mixing judgment.
Position: east wall + west wall first reflection points + splayed/absorptive front
Height: 120 cm AFF (bottom edge) · located by mirror method from mix position
| Element | Location | Previous | acoustics5 / S3 | Key benefit |
|---|---|---|---|---|
| Editing Suite | East zone (B312-2) | 8.56 m² isolated room | Removed — merged into Video/Podcast | Frees the east zone; editing needs no isolated room |
| Video/Podcast | East zone (B312) | 11.23 m² · 2.75 m ceiling | 19.78 m² · 3.40 m high ceiling (measured) | Larger, better modes (Schroeder 130 Hz); flexible for video + podcast |
| Wall 7 + D4 | Video ↔ Editing partition | STC 48 wall + STC 48 door | Removed entirely | Two weak partition elements eliminated |
| D5 Door (new) | Control · south wall | — | STC 50 · 90×220 · opens out | Dedicated Control entry without transiting VO / buffer |
| Control Room | Side walls E + W + front | 0 flat panels | 3× 1200×600mm | Eliminates first-reflection comb filtering |