HVAC Penetrations

HVAC installation guide covering Daikin VRF cooling, fresh air ventilation, silencer schedule, and wall penetration sealing requirements.

CONCEPTUAL ACOUSTIC REQUIREMENT ONLY

This HVAC layout is the acoustic performance requirement only. Final duct sizing, equipment selection, silencer specifications, airflow rates, pressure drop calculations, and installation drawings must be completed by a qualified MEP/HVAC engineer. The silencer attenuation values in this document are acoustic targets — they are not final engineering specifications.

MEP note: Silencer selection must be verified against octave-band noise data (63–4000 Hz) from actual fan manufacturer curves.

System Overview

System 1: Daikin VRF Cooling

Type Variable Refrigerant Flow (Daikin VRF)
Indoor units 3 wall-mounted IDUs
IDU-04 Serves VO Live only — dedicated (north wall, west side)
IDU-03 Serves Control Room only — former Editing branch capped/sealed at trunk (north wall, Control zone)
IDU-05 Serves Video/Podcast only — dedicated (north wall, Video/Podcast side)
Outdoor unit (ODU) 1 unit, south exterior wall

System 2: Fresh Air Ventilation

Purpose Outside air supply with acoustic silencers
Distribution Plenum-based via 76 cm ceiling plenum (audio rooms; Video/Podcast uses a perimeter MEP bulkhead — see note)
Silencer runs 5 runs (A, B, B1, B2, C) — see schedule below

Silencer Schedule

Run Serves Length Attenuation Terminal Velocity NC Max
A VO Live (dedicated) 1500 mm 40 dB 1.5 m/s NC-12
B Control trunk 1000 mm 25 dB 2.0 m/s NC-18
B1 Control branch 500 mm 15 dB 2.0 m/s NC-18
B2 Control (former Editing branch, retained/re-rated) 300 mm 10 dB 2.5 m/s NC-18
C Video/Podcast (dedicated) 1000 mm 25 dB 2.0 m/s NC-18
IDU-03 — Control Only (Former Editing Branch Capped):

The former Editing branch off IDU-03 is capped and sealed at the trunk. No crossover duct remains, so there is no IDU-03 room-to-room flanking path.
Silencer: Run B2 is retained and re-rated to serve Control only (NC-18).
Risk level: LOW (single-room service, no crossover).

VO Live NC-12 — Achievable with Dedicated IDU-04:

NC-12 achievable — dedicated IDU-04 eliminates shared chassis flanking from Control Room. No crossover duct to VO Live.
Confirm: IDU-04 self-noise at minimum fan setting ≤ NC-12 curve with supplier.

Wall Penetration Rules

MANDATORY — All Penetrations Must Comply:
  1. Every duct penetration: oversized sleeve with 25 mm annular gap, packed with Rockwool + sealed with acoustic sealant on both faces
  2. No back-to-back penetrations on opposite walls — offset by minimum 600 mm to prevent direct sound path
  3. Daikin VRF refrigerant pipes: 32 mm sleeve, foam backer rod, acoustic sealant both faces
  4. Buffer spine = ONLY permitted duct routing path between east/west zones — no ducts through perimeter walls between adjacent rooms
  5. Plenum barrier walls: full-height gypsum from ceiling tile to structural slab at every partition — sealed with acoustic caulk on both faces

Penetration Sealing Detail

LayerProductSpecification
1. Sleeve Galvanized steel 25 mm larger than duct on all sides, fixed to wall structure
2. Packing Rockwool Fill annular gap, compressed to 80% density
3. Sealant Acoustic sealant (Tremco or equiv.) Full perimeter, 25 mm depth minimum, both faces
4. MLV boot 1 lb/ft² mass-loaded vinyl Wrap around duct ±150 mm from wall face
5. Fire collar Intumescent collar Both sides of wall — required for fire compartmentation

Daikin VRF Refrigerant Pipe Sealing

LayerProductSpecification
1. Sleeve PVC or steel 32 mm diameter, centered on pipe
2. Backer rod Closed-cell foam backer rod Fill annular gap, compress to contact
3. Sealant Acoustic sealant Both faces, full perimeter

Plenum Barriers

Barrier LocationMaterialPurpose
Above buffer spine 15 mm Knauf Soundshield Plus, sealed to slab Prevents flanking between east and west zones
Above VO/Control partition 15 mm Knauf Soundshield Plus, sealed to slab Prevents flanking between VO Live and Control Room (plenum path)
MLV curtains at duct crossings 1 lb/ft² MLV, ceiling to slab Acoustic curtain wraps around ducts where they cross plenum barriers
Video/Podcast — Perimeter MEP Bulkhead + HVAC Service Hatch:

The Video/Podcast room keeps a HIGH 340 cm clear ceiling over the open floor. The hanging MEP services (IDU-05 refrigerant/condensate and the fresh-air/black duct) are boxed into a deep perimeter bulkhead rather than a full dropped plenum, preserving the 340 cm clear height in shot. This bulkhead is also built as a real bass device (≥300 mm mineral-wool fill + sealed cavity, α₁₂₅≈0.55 — the deep perimeter bass soffit).
Access: provide an HVAC service hatch in the perimeter bulkhead for silencer Run C, dampers, and refrigerant joints — sealed acoustically when closed.

IMPORTANT DISCLAIMER: The above is the acoustic performance requirement. Final HVAC design, equipment selection, and installation drawings are to be produced by the MEP engineering team. All silencer specifications, duct sizes, and penetration locations must be verified by a qualified mechanical engineer before procurement or installation.