STC Wall Comparison

STC ratings for all wall assemblies, doors, and the observation window. Field ratings are typically 3–7 dB lower than laboratory values.

STC Comparison — All Elements

STC 0STC 20STC 40STC 50STC 60STC 70W1 — North concreteSTC 65W2 — West diagonal (existing gypsum + new inner leaf)STC ~60W3 — East server wallSTC 62W4 — South rebuiltSTC 50W5 — Buffer spineSTC 55W6 — VO/Control partitionSTC 53D1 — South entry (Video/Podcast)STC 50D3 — Control ↔ VOSTC 45D5 — Control external (opens out)STC 50OW-1 window — ObservationSTC 50
W1W2W3W5W4W6D1D3D5OW-1

Wall Schedule

WallNameLab STCField STC Est.Thickness
W1North concrete (street — the only concrete wall)6558–62variable
W2West diagonal — existing gypsum + NEW independent inner stud leaf (PW-02)~60 (class)55–60existing leaf + ≥25mm gap + 70mm studs/RWA45 + 2×12.5 SoundBloc+GG
W3East — existing gypsum leaf to B313 SERVER ROOM + NEW decoupled stud leaf (PW-04)6255–5916cm new stud leaf + 100mm existing air gap (kept UNFILLED) = 26cm total buildup
W4South — existing gypsum partition lined/rebuilt to STC 50 (PW-03; D1/D5 framed openings, steel subframes)5044–4815cm
W5Buffer spine — NEW BUILD (W-07)5549–5315cm
W6VO/Control partition5347–5112cm

Door & Window Schedule

ElementLocationLab STCField STC Est.
D1South entry → Video/Podcast5044–48
D3Control ↔ VO4540–43
D5Control external (opens out)5044–48
OW-1 windowObservation5044–48

Technical Notes

Mass-Air-Mass (MAM)

Two gypsum layers with air gap — the gap resonance frequency must be above 200Hz for audible range effectiveness. Below this frequency, the double-leaf system can actually perform worse than a single leaf of equal total mass.

Green Glue

Constrained layer damping compound — adds 5–8 STC points vs single-layer gypsum. Applied wet between two rigid layers, it converts vibration energy to heat. Used on the South lining/rebuild (W4), buffer spine (W5), the VO/Control partition (W6), and the new west (W2/PW-02) and east (W3/PW-04) inner stud leaves.

RSIC Clips

Resilient sound isolation clips decouple gypsum from structure, eliminating direct vibration path. RSIC-1/A237R clips are used on the NORTH concrete wall only (W1) — the west, south and east walls are gypsum (S3-SITE-TRUTH), so they get independent/decoupled stud leaves instead of clips-on-mass.