Field STC test kit (or 3rd-party lab) · — Qty: optional ASTM E336
Build sequence
1 Measure RT60 (per room)
Sweep each room with UMIK-1 + REW; source at 1/4, mic at 3/4. Compare per octave band to target (report Sabine + Eyring).
2 Measure NC at design airflow
With HVAC at design airflow, measure octave-band SPL at each grille with a Class-2 SLM; rate vs NC target (VO NC-12 etc.).
3 Field STC test
Test isolation across the partitions + doors/window (ASTM E336) — confirm field STC meets the balanced-partition targets.
4 Punch list & sign-off
Log results, fix any fails (e.g., add Studio LF trapping, reseal a door), re-test, and sign off when all rooms pass RT60 + NC.
Golden rule: Don't sign off on paper — measure. RT60 (Sabine+Eyring) + NC at design airflow + field STC, room by room. Be ready to add LF trapping (Studio) or reseal an opening, then re-test.