HVAC Bill of Materials

Complete HVAC equipment and silencer specifications · acoustics5 · Audience: MEP contractor, procurement

AC Acoustic Critical HP Hold Point — stop work, obtain sign-off

System Overview

System: Daikin VRF (Variable Refrigerant Flow) — NOT Samsung. 3× indoor units, 1× outdoor unit. 6 fresh air terminals (2 per room).

Indoor Unit Schedule

Unit IDRoom servedTypeLocationNC targetNotes
IDU-04VO LiveDedicatedNorth wallNC-12 maxAC
IDU-03Control RoomDedicatedNorth wallNC-18 max
IDU-05Video/PodcastDedicatedNorth wallNC-18 max
ODUOutdoor unitCompressor/condenserSouth sideDaikin VRF
Indoor/outdoor unit model and cooling capacity per mechanical design (architect MEP drawings B302–B308) — not fixed by this acoustic study. Do not procure specific Daikin VRF models from this table alone.

Silencer Schedule

All silencer runs are independent. IDU-03 now serves Control Room only, so the former B1/B2 crossover no longer applies.
RunServesLengthAttenuationMax velocityNC limit
AVO Live1500 mm40 dB1.5 m/sNC-12 AC
BControl trunk1000 mm25 dB2.0 m/sNC-18
B1Control branch500 mm15 dB2.0 m/sNC-18
B2Control branch — RETAINED + re-rated (BOQ HV-02, verify 125Hz insertion loss)300 mm10 dB2.5 m/sNC-18
CVideo/Podcast1000 mm25 dB2.0 m/sNC-18
Attenuation values shown are broadband targets. Confirm insertion loss per octave band with the silencer supplier against the room NC targets before procurement.

Duct Accessories

ItemSpecNotes
Flexible canvas connectorsBoth ends of every silencerAC
Duct hangersNeoprene-isolated · every 600mm
Fresh air terminals6 total · 2 per room

Vibration Isolation Materials

ItemSpecNotes
IDU anti-vibration mountsSpring/neoprene isolators · 25mm min deflectionAC
Duct hanger isolatorsNeoprene pads · every 600mm
Flexible connectorsCanvas flexible duct connectorsBoth ends of every silencer AC

NC Performance Targets

RoomNC targetCritical
VO LiveNC-12AC Lowest — highest sensitivity mic use
Control RoomNC-18
Video/PodcastNC-18

Hold Points

HPDescription
HP 6.0Acoustic consultant approves silencer submittals before ordering
HP 6.1Velocity and attenuation verified in situ before closing walls